Tecnomatic Corp

Series

R3F — Three-Phase Filter Reactors

Harmonic filter (detuning) reactors for PFC capacitor banks — P = 7% / 14%, 400 V

CEIEC 60076-6
R3F — Three-Phase Filter Reactors

Three-phase harmonic filter reactors that detune power-factor-correction capacitor banks away from system harmonics, protecting the capacitors and limiting resonance. Available in two detuning factors — P = 7% (tuned to 189 Hz, linearity > 1.73 x I rms) and P = 14% (tuned to 134 Hz, linearity > 1.37 x I rms) — rated from 6.25 to 50 kVAR at 400 V 50 Hz. Screw terminals on the smaller ratings, busbar terminals on the larger ones.

Key Features

  • Detuning filter reactors for PFC capacitor banks
  • Two detuning factors: P = 7% (189 Hz) and P = 14% (134 Hz)
  • Linearity > 1.73 x I rms (P=7%) / > 1.37 x I rms (P=14%)
  • Screw terminals up to 12.5 kVAR, busbar from 20 kVAR
  • Copper / aluminium windings

Mounting

Floor / panel mount

CEIEC 60076-6
R3F — Three-Phase Filter Reactors — METH catalogue

METH Catalogue

Dimensions & data chart

Full dimensional drawing, code matrix, and electrical data (losses, efficiency, Ucc, inrush) for this series in the METH Transformer Catalogue — page 26.

View dimensional drawing & data chart (METH Catalogue p. 26) →

Technical Data

Specifications

Inches shown as primary unit, mm as secondary where applicable. Custom voltages and ratings available — contact us for engineered configurations.

ModelVA / kVAPrimary VoltageSecondary VoltageCertifications
R3F-7 - P = 7% / 189 Hz / 400 V / linearity > 1.73 x I rms
R3F-7-400-6,256.25 kVAR400 V6.13 mHCE · IEC 60076-6
R3F-7-400-1010 kVAR400 V3.84 mHCE · IEC 60076-6
R3F-7-400-12,512.5 kVAR400 V3.07 mHCE · IEC 60076-6
R3F-7-400-2020 kVAR400 V1.92 mHCE · IEC 60076-6
R3F-7-400-2525 kVAR400 V1.53 mHCE · IEC 60076-6
R3F-7-400-4040 kVAR400 V0.96 mHCE · IEC 60076-6
R3F-7-400-5050 kVAR400 V0.77 mHCE · IEC 60076-6
R3F-14 - P = 14% / 134 Hz / 400 V / linearity > 1.37 x I rms
R3F-14-400-6,256.25 kVAR400 V13.27 mHCE · IEC 60076-6
R3F-14-400-1010 kVAR400 V8.29 mHCE · IEC 60076-6
R3F-14-400-12,512.5 kVAR400 V6.63 mHCE · IEC 60076-6
R3F-14-400-2020 kVAR400 V4.15 mHCE · IEC 60076-6
R3F-14-400-2525 kVAR400 V3.32 mHCE · IEC 60076-6
R3F-14-400-4040 kVAR400 V2.07 mHCE · IEC 60076-6
R3F-14-400-5050 kVAR400 V1.66 mHCE · IEC 60076-6

Available from our Italian warehouse. Lead times and pricing on request.

Use Cases

Typical Applications

Detuned PFC banks

Protect power-factor-correction capacitors in harmonic-rich networks.

Harmonic mitigation

Reduce resonance risk on networks with VFDs and non-linear loads.

Industrial switchboards

Capacitor-bank panels in plants and commercial buildings.

Utility reactive compensation

Medium and large reactive-compensation installations.

Get a Quote

Request a Quote — R3F